Detector technical parameters
- Power supply: AC 220V 50Hz
- Sensitivity: 10% L.E.L. (lower explosion limit)
- Response time: <30 s
- Power consumption: in normal operating mode <1.5 W – alarm 3 W
- Operating temperature: -15 ° C – 50 ° C
- Humidity: <97% RH (relative humidity)
- Warning volume:> 90dB (decibels) at a distance of 1m from the detector
- Possibility of connecting to a 12V DC solenoid valve
- Polarity: white conductor (+) positive, black conductor (-) negative
- Weight: 250 g
- Detective gases: natural gas (methane), LPG (butane, propane)
Technical parameters of the valve
- Gas types: natural gas (methane) and LPG (butane, propane)
- Solenoid body: brass alloy, nickel
- Sealing material: NBR / EKM rubber
- Operating temperature: -10 ° C – + 50 ° C
- Connecting thread: G1 / 2 “DN15, G3 / 4” DN20, G1 “DN25
- Opening: manual
- Closing – 9 V DC – 12 V voltage or manual
- Closing current:> 1.5 A (pulse)
- Closing time: > 1s
- Polarity: white wire (+) positive, black wire (-) negative
- Maximum pressure: 500mBar (max. 1 bar pressure test after 20 minutes)
Reviews